You'll find that our CDCS exam questions frequently feature detailed scenarios and practical problem-solving exercises that directly mirror industry challenges. Engaging with these CDCS sample sets allows you to effectively manage your time and pace yourself, giving you the ability to finish any EXIN EPI Certified Data Centre Specialist practice test comfortably within the allotted time.

Question # 11

What is the floor loading requirement for a Rated-3 data center according to ANSI/TIA-942?

A.

7.2 kPa

B.

8.4 kPa

C.

12 kPa

D.

15 kPa

Question # 12

When shielding material reaches its saturation point, what will be the impact?

A.

The shielding material will reach its optimal shielding performance state.

B.

The shielding material will no longer be able to attenuate (reduce) additional EMF.

C.

The shielding material will increase its permeability factor.

D.

The shielding material will reach its maximum electrically charged state.

Question # 13

A computer room needs to be fitted out with a gas-based fire suppression system. The computer room will be a high-density data center with about 30% of the racks being closed circuit cooling blade-center racks.

Should the supplier of the fire suppression system be informed on the design of the racks?

A.

No, cooling and design of racks have no influence on the fire suppression system design.

B.

Only when the rack height obstructs a potential fire suppression release point.

C.

Yes, the design of the racks has an influence on the fire suppression system design.

D.

Only when the racks might block access to the fire panel.

Question # 14

What is a potential disadvantage of using water mist as a fire extinguishing system?

A.

It only uses 10% of the water normally used in a water-based fire suppression, which might not be enough to suppress the fire

B.

It will rapidly increase the humidity level in the data center, which can cause a potential risk for the operation of the equipment

C.

It extracts oxygen from the air creating a potential risk for humans inside the computer room

D.

It has droplets that are too small (100-120 microns) so it can only be used for small fires

Question # 15

EMF shielding material needs to be installed as EMF levels from the transformer room into the computer room are measured at 100 mG. The transformer room is ~10 meters away, separated by a corridor. Where should shielding be installed?

A.

It does not matter; either close to the transformer room or computer room is okay

B.

As close as possible to the transformer room

C.

As close as possible to the computer room

D.

Shielding is not required as 100 mG is within acceptable levels

Question # 16

Given: A = attenuation in dB, R = real measured value, M = maximum acceptable value. Which formula should be used to calculate the required attenuation factor of EMF shielding material?

A.

A = 10 log (R/M)

B.

A = 20 log (M/R)

C.

A = 10 log (M/R)

D.

A = 20 log (R/M)

Question # 17

Where should raised-floor installation start?

A.

Point A (entrance corner)

B.

Point B (side wall)

C.

Point C (center of the room)

D.

Point D (corner opposite entrance)

Question # 18

Management has requested a 15-minute battery bank assuming full load on the UPS. The UPS vendor has provided the following specifications of the UPS:

• Rated power: 30 kVA

• Rectifier input voltage: 400 V/3 phase

• Rectifier input power factor: 0.8

• Battery rated voltage: 384 V

• Number of cells: 192

• End of discharge voltage: 308 V

• Inverter output voltage: 400 V/3 phase

• Inverter output power factor: 0.8

What information is missing to perform the battery calculation?

A.

UPS efficiency

B.

Inverter efficiency

C.

Load imbalance on the phases

D.

Available battery charging current

Question # 19

FM-200 is phasing out as a halocarbon gas and management has decided to replace this with the more environmentally friendly Novec-1230 gas. Should you use exactly the same formula and parameters to calculate the gas content for the Novec-1230 gas?

A.

Yes, as long as the temperature in the computer room has not changed

B.

Yes, if you take the difference between the net and gross volume into account

C.

Yes, as long as you use the same units of measure (kg/m³ or lbs/ft³)

D.

Yes, if you change the S-factor of the formula to reflect the gas type used

Question # 20

Maximum exposed area of fire-rated glass is 2 m², but the window is 5 m². What is the best option?

A.

Replace with normal glass

B.

Split into two equal parts with silicone

C.

Split into two equal parts with aluminum frame

D.

Split into smaller parts within 2 m² using fire-rated frames