EXIN EPI Certified Data Centre Specialist

Last Update 17 hours ago Total Questions : 120

The EXIN EPI Certified Data Centre Specialist content is now fully updated, with all current exam questions added 17 hours ago. Deciding to include CDCS practice exam questions in your study plan goes far beyond basic test preparation.

You'll find that our CDCS exam questions frequently feature detailed scenarios and practical problem-solving exercises that directly mirror industry challenges. Engaging with these CDCS sample sets allows you to effectively manage your time and pace yourself, giving you the ability to finish any EXIN EPI Certified Data Centre Specialist practice test comfortably within the allotted time.

Question # 4

You have three UPS systems connected in parallel. The UPS systems have an imbalance in the load sharing of approximately 20%.

What should you recommend?

A.

Review the cable lengths of each UPS to the common busbar

B.

Nothing, there is no reason for any concern

C.

Review the common mode noise levels within the computer room

D.

Review the harmonics levels within the computer room

Question # 5

What is the floor loading requirement for a Rated-3 data center according to ANSI/TIA-942?

A.

7.2 kPa

B.

8.4 kPa

C.

12 kPa

D.

15 kPa

Question # 6

What is a significant difference between a halocarbon gas-based fire suppression system and an inert gas-based fire suppression system?

A.

Inert gas has smaller-sized gas containers than halocarbon gas.

B.

Inert gas harms the environment and halocarbon gas does not.

C.

Halocarbon gas works on the basis of heat removal and inert gas works on the basis of oxygen reduction.

D.

Halocarbon gas works on the basis of oxygen reduction and inert gas works on the basis of heat removal.

Question # 7

When designing a data center network, your company wants to minimize the number of network cables to install. What type of physical cabling layout would be the best choice?

A.

Top of Rack (ToR) design

B.

End of Row (EoR) design

C.

Star network design using coaxial cables

D.

It does not matter as the number of switches is not influenced by the physical cabling layout

Question # 8

Which formula is correct?

A.

Phase-to-Neutral Voltage = Phase-to-Phase voltage * 1.732

B.

Phase-to-Neutral Voltage = Phase-to-Phase voltage /1.732

C.

Phase-to-Neutral Voltage = Phase-to-Neutral voltage * 1.732

D.

Phase-to-Neutral Voltage = (Phase-to-Phase voltage * 1.732) / Phase-to-Neutral Voltage

Question # 9

When are the wet bulb and dry bulb temperatures identical?

A.

When the dry bulb's temperature is at the lowest allowable temperature for IT equipment as per ASHRAE

B.

When the dry bulb's temperature is at the highest allowable temperature for IT equipment as per ASHRAE

C.

When the relative humidity is at the best practice value for relative humidity, being 50% RH

D.

When the relative humidity is 100%

Question # 10

The data center has been in operation for about 1 year and 2 months. The dust levels in the computer room are relatively high.

What is the most likely root cause?

A.

The cleaning crew is not doing their work properly

B.

Every computer room has high dust levels due to constant high-speed air movement

C.

Low pressure in the computer room

D.

Floorboards are most likely not fitted correctly